positive-isolation

Spectacle Blind: Also referred to as a figure 8 blank, this has the same pressure retaining characteristics as a blind 

skillet but has 2 ends, one solid (blind) and one open. 

 



 

POSITIVE ISOLATION

 

 

Rev Date:  March 2015 



Page 8 of 8 

This document is uncontrolled when printed.

 

Canada 



Appendix B – Revision Record 

Page# 

March 16, 2015 

Previous Information

Change Assessment

Work must not start until the absence of energy and/or 



harmful substances has been confirmed. 

 

Changes in work scope require a revalidation of the isolation 



method prior to continuing with the work. 

None 


Low – Life Saving Rules 

requirement. 

Pressure must be eliminated from a system prior to adjusting 



or maintaining attached equipment that has the potential to 

release pressure (e.g., adjusting fittings, piping, etc.). This 



does not apply to equipment that has been engineered to be 

adjusted under pressure (e.g., greasing certain components 

such as valves, etc). Always verify with manufacturer 

maintenance instructions or engineering prior to servicing 

under pressure. 

None 


Low – Clarification of 

expectations related to 

investigations and audits. 

Non‐code skillets and blinds can only be used in non‐pressure 



environments. 

None 


Low – Clarification of 

engineering requirements. 

Workers must be informed of the alternative methods and 



instructed in any applicable work procedures.  

None 


Low – Clarification of 

regulatory requirements. 

Each Business Unit will maintain a listing of approved 



alternative means of isolations. 

 

Single valve isolations may only be used in the following 



circumstances unless an engineering assessment is 

completed: 

• Opening equipment to establish positive isolation (i.e., 

install blinds). 

• Pig sending and receiving 

Single valve isolation requires the use 

of sound judgment. If any doubt exists 

about the appropriateness of single 

valve isolation, use one of the other 

methods of isolation  

Examples of operations where the use 

of single valve isolation may be 

appropriate include: changing pressure 

gauges, cleaning sight glasses, 

replacing needle valves, pig launching, 

replacing fluid chokes, etc. 

Low – Clarification of 

regulatory requirements. 

Additional definitions added for clarity around isolation 



methods and valve types 