Installation Guide: IntelliFlo3 and IntelliPro3 vsf pool Pump



Yüklə 6,98 Mb.
Pdf görüntüsü
səhifə15/37
tarix16.12.2023
ölçüsü6,98 Mb.
#182724
1   ...   11   12   13   14   15   16   17   18   ...   37
intelliflo3-pro3-vsf-install-guide

Inputs, page 5
 for more information.
+12V
*
RED
*
DATA–
GREEN
GND
*
BLACK
*
DATA+
YELLOW
RS-485 WIRING
DIGITAL INPUTS**
(Low Voltage)
RS-485
(Low Voltage)
*
Note
:
When connecting to a 
Pentair Automation System, 
connect 18 to 24 AWG, two-
conductor cable to the DATA+ 
and DATA- terminals only. 
If needed, 12V and Ground 
terminals are also provided.
Refer to the automation system 
manual for further details.
PUMP RELAYS**
0-300 VAC, 0-48 VDC
5A
(Left-side)
Salt Chlorine Generator
Pool Light / Transformer
16A
(Right-side)
Booster Pump
Single Speed Pump
Spa Blower


5
INTELLIFLO3™ VSF / INTELLIPRO3™ VSF Variable Speed and Flow Pump Installation and Maintenance Guide
Relay Control Board Digital Inputs
If the optional Relay Control Board Kit (P/N 356365z) is installed, 
the board's digital inputs can be connected to an automation 
system in order to control four customizable speed or flow 
programs.
If using digital inputs, schedules programmed via 
the Pentair Home app or drive touchscreen must be deleted.
Note:
If multiple external input triggers are received, 
programs will follow the following priority: 
PROGRAM 4 > 3 > 2 > 1.
Note:
If the pump has been stopped via the ON/STOP button 
(ON/STOP LED is solid red), ON/STOP must be pressed again 
before the pump will operate.
When a low voltage signal is received by a control board digital 
input, the pump will run the program set to that specific digital 
input. This digital input program will override any scheduled 
programs, automation or manual input.
Note:
Refer to the 
Pentair Home User's Guide (P/N 356088) 
for 
instructions on viewing and editing the pump programs.
Note:
Refer to the 
Relay Control Board Installation Guide (P/N 
356994) 
for instructions on installing the control board.
The Relay Control Board also provides a +12V Output Signal 
(marked VOUT) that can be used to trigger its own Digital Inputs.
This output signal is the recommended input for Speed Digital 
Inputs. 
The output signal will need to be switched via an External Control 
(i.e. automation relay, external system component switch) to 
activate the desired speed program.
PROGRAM 4 > 3 > 2 > 1

Yüklə 6,98 Mb.

Dostları ilə paylaş:
1   ...   11   12   13   14   15   16   17   18   ...   37




Verilənlər bazası müəlliflik hüququ ilə müdafiə olunur ©www.azkurs.org 2024
rəhbərliyinə müraciət

gir | qeydiyyatdan keç
    Ana səhifə


yükləyin