Protecti ve coati ng pci visc onal ® Technical Data Sheet 300 Edition October 2020 for wate rproofin



Yüklə 240,04 Kb.
Pdf görüntüsü
tarix02.01.2022
ölçüsü240,04 Kb.
#47243
PCI Visconal® Technical data sheet EN



Protecti

ve coati

ng

PCI Visc

onal

®

Technical Data Sheet 300

Edition October 2020

for wate

rproofin

g storag

e rooms

 for fuel

 oil

P-57.001

VMPA

M

at

er

ia

lp



fun

gs- u

nd Forsc

hun

gs

an

sta

lt

MPA

KARLSRUH

E

PCI Augsburg GmbH

Werk 1

Storage room for fuel oil coated with 

PCI Visconal.

For indoor use.



For walls and floors.

For coating surfaces made of 



concrete, render/plaster and screed

for collecting trays and rooms for fuel

oil EL (common fuel oil) and 

transformer oil.

Fields of application

Protects the groundwater, durably



waterproofs collecting trays and

rooms for fuel oil EL, diesel fuel with 

≤ 0.5% organic fraction and 

transformer oil.

Bridges cracks up to a width of 



0.2 mm arising in the substrate at a

later stage.

Easy to clean, leaked fuel oil EL and



transformer oil can be easily 

vacuum-cleaned or wiped off from the

PCI Visconal coating without leaving

any residues.

Temperature resistant, multi-purpose



use for collecting trays in the interior

as mentioned above.

Officially tested in accordance with



the building and test principles for

water protection coatings issued by

Deutsche Institut für Bautechnik 

Berlin (German Institute for Building

Technique Berlin), by Institut für 

Massivbau und Baustofftechnologie

(Institute for Solid Building and 

Building Material Technology) at the

University Karlsruhe.

Features and benefits




Technical Data Sheet

PCI Visconal

®

Material


Application

* At +23°C and 50% relative humidity. Higher temperatures reduce, lower temperatures increase the times given.

Material base

synthetic resin dispersion based on a vinyl acetate-ethylene-copolymeride

Components

single component

Density

approx. 1.6 g/cm³

Shelf life

min. 12 months; store frost free, no permanent storage over +30°C

Packaging size

color grey

color red

5 l pail


stock no. 1217/8

5 l pail


stock no. 1227/7

Consumption

- base coat

min. 125 ml/m² of PCI Visconal grey

- 1

st

top coat



min. 250 ml/m² of PCI Visconal red

- 2


nd

top coat


min. 375 ml/m² of PCI Visconal grey

= 500 ml/m² of PCI Visconal grey

+ 250 ml/m² of PCI Visconal red

Coverage (example)

covers approx.

- 10 l pail of PCI Visconal grey

+ 5 l pail of PCI Visconal red

20 m²


Total layer thickness

- minimum

450 μm

Processing temperature



+5°C to +25°C (substrate temperature)

Drying time*

- base coat PCI Visconal grey

min. 8 hours

- 1

st

top coat PCI Visconal red



min. 8 hours

- 2


nd

top coat PCI Visconal grey

min. 8 hours

Able to bear weight after complete drying

after 7 days at the earliest

Technical data

Requirements



Cracks in the retaining walls and the

bottom of the collecting pans and

rooms caused by setting or 

contraction must be prevented by 

taking constructive measures.

Expansion joints in collecting pans

are not allowed. Please ask for

technical advice if expansion joints

already exist.

Water acting on the reverse side of

the coating must be prevented, 

waterproofing may be required in 

accordance with DIN 18195 – Water-

proofing buildings – dimensioning and

construction.

Areas of concrete, plaster/render and

screed must be at least 28 days old,

dry, able to bear weight and void free.

The substrate must be structurally

sound, rough, non-slip and fine-pored

in the surface. It must be free from

honeycombs, voids, cracks and 

ridges, dust, tar, pitch, forming oil and

other residues which could impair 

adhesion. Edges must be broken.

The substrate must be free from a



dusty or sandy surface. Plaster/render

and screed must have a firm bond to

the supporting structural elements

and/or retaining walls and the bottom.

It is not allowed to smooth the 

surface with the steel trowel, but it

must be rubbed down with a wooden

board. It is not allowed to powder the

surface with cement. A firmly bonding

render is to be applied to brickwork

and concrete areas which are not in

compliance with these requirements.

Pipe culverts below the maximum

possible liquid level as well as 

expansion joints are not allowed!

The coating must not be applied until

the before-mentioned structural 

requirements are given.

The surface must be approved by

the company carrying out the

coating work before applying the

coating!


Preparation

Mechanical cleaning with a hard

broom, steel brush or industrial type

vacuum cleaner. Break-outs can be

repaired with the following 

PCI products: PCI Pecihaft bonding

slurry, PCI Legaran RP corrosion 

protection, PCI Nanocret R4 PCC/R2

repair mortar, PCI Nanocret FC 

concrete smoothing compound, and

PCI Repament or PCI Periplan in floor

areas.

Internal corners are to be formed as



covings with PCI Repafix.

Preparation of substrate




Technical Data Sheet

PCI Visconal

®



A minimum of one base coat and two



top coats are required to produce an 

oil-proof coating. To make the number

of applied coats visible, the second and

any further coats should only be applied

as far up as leaving 1 cm of the previous

coat visible. Every coat must be applied

pore-free and until saturated. Every layer

must be completely dry before applying

the next one.

Priming


1

Dilute PCI Visconal grey with 50% of

water (volume 2 : 1) and thoroughly brush

into the substrate.

2

Allow the base coat to dry for at least 



8 hours (at +23°C).

Coating


3

Apply the first top coat of undiluted 

PCI Visconal red to the primed substrate

using a trowel. Allow to dry for at least 

8 hours.

4

Apply undiluted PCI Visconal grey as



second top coat when the first top coat

is dry.


5

The coating is completely dry and able

to bear weight after 7 days at the 

earliest.

Application procedure of PCI Visconal

The first top coat with PCI Visconal (red) can be applied to the surface 

primed with PCI Visconal (grey) diluted with 50% of water after a drying

time of approx. 8 hours.

An oil-proof coating requires one base coat and two top coats; therefore

the second top coat with PCI Visconal (grey) can be applied after a drying

time of another 8 hours.

PCI Visconal is suitable for coating 



concrete surfaces (C20/25 according to

DIN EN 206-1:2001-07; DIN 1045-

1:2008-08; DIN 1045-2:2008-08; 

DIN 1045-3:2008-08), plaster surfaces

(PIII according to DIN V 18550:2005-04)

and screed surfaces (CT 25 - F4 

according to DIN 18560-3:2006-03; 

DIN 18560-7:2004-4; DIN 18560-

1:2004-04; DIN 18560-1/A1:2008-07;

AGI A 12-1:1997-06) in collecting trays

and catchment areas for:

- extra light heating oil according to 

DIN 51 603-1,

- unused combustion engine oils and

motor vehicle transmission oils and

- mixtures of saturated and aromatic 

hydrocarbons with an aromatic content

of ≤ 20% by weight and a flash point 

> 55 °C inside buildings closed on all

sides and outdoors.

Do not use PCI Visconal at substrate



temperatures below +5°C and above

+25°C (maximum 50% relative 

humidity).

Drying times must be followed!



Make sure that the coat applied is not

too thin.

Clean tools and mixing buckets with



water immediately after use; the

cured product can only be removed

by mechanical scraping.

The present guideline regulated by



law does not require PCI Visconal

coatings for catchment areas to be

carried out by a professional 

company. In case of a storage 

quantity over 10,000 liters the work

should be done by a professional

company.

Please note




Technical Data Sheet

PCI Visconal

®



PCI Visconal must be protected by a



fireproof covering when installing

tanks welded in the cellar.

PCI Visconal must be protected from



permanent exposure to water.

Protective coatings are required when



exposed to vehicular traffic. They can

be applied 7 days after the second

top coat. Suitable protective coatings

is e.g. a cement screed on an 

isolating layer or plastic boards.

Protective measures for the PCI Visconal coating

Treated goods in accordance with 

regulation (EU) No 528/2012:

Contains biocide (in-can preservative):

1,2-BENZISOTHIAZOL-3(2H)-ONE, 

2-Methyl-2H-isothiazol-3-one, mixture

of: 5-CHLORO-2-METHYL-2H-ISOT-

HIAZOLIN-3-ONE and 2-METHYL-2H-

ISOTHIAZOL-3-ONE (3:1). May produce

an allergic reaction. Keep out of reach

of children. Wear protective gloves. Do

not breathe aerosol. Protect eyes where

there is risk from splashing. In case of

contact with eyes thoroughly rinse with

water. If the eye irritation does not ease

off within a few minutes seek medical

advice. If medical advice is needed,

have product container or label at hand.

Giscode BWS20

For further information: see PCI Material Safety Data

Sheet.


Information on the safe use

Consultations at the workplace, supple-

mentary information, testing certificates

and sample descriptions can be reques-

ted from professional advisors and at

the company headquarters.

Services for architects and designers

PCI participates in an area-wide waste

disposal system for sales packaging

completely emptied. DSD – Duales 

System Deutschland (Dual System 

Germany, contract number 1357509) is

our partner for waste disposal. PCI sales

packaging completely emptied can be

disposed of via DSD in accordance with

the symbol printed on the packaging. 

For further information on disposal see

the safety and environmental information

in the price list and also on the Internet at

http://www.pci-augsburg.eu/de/service/

disposal instructions.html.

Disposal of emptied PCI sales packaging

PCI Augsburg GmbH

Piccardstr. 11 · 86159 Augsburg

Tel.  +49 (8 21) 59 01-0

Fax +49 (8 21) 59 01-372

www.pci-augsburg.de

The working conditions on construction sites and the areas of application of our products are highly diverse. 

In the technical data sheets, we can only give general instructions for the use of our products. These are in

 accordance with the information currently available to us. Architects, engineers and the users of our products are

under an obligation to verify the suitability of our products and the feasibility of using them for their specific

 applications. For applications not explicitly referred to under “Area of applications” in the technical data sheet,

 architects, engineers and users of our products are under an obligation to obtain technical advice from PCI. In the

event that the product is used outside the scope of applications defined in the technical data sheet without

 obtaining the advice of PCI, the user of the product will be liable for any loss or damage arising as a result of the

use of the product. All the descriptions, drawings, photographs, data, conditions, weights, etc. stated in the

 technical data sheet may be changed without notice and do not represent the agreed properties of the product.

Recipients of our products are under an obligation to comply with any proprietary rights and any applicable laws

and regulations under their own responsibility. If trade names used by other companies are referred to in this

 technical data sheet, such references do not represent a recommendation for the use of such products and do

not  exclude  the  use  of  other  comparable  products.  The  information  which  we  provide  only  describes  the

 characteristics  of  our  products  and  services  and  does  not  represent  any  guarantee.  A  guarantee  of  specific

 properties or the fitness of the product for a specific purpose cannot be derived from the information which we

provide. We will not be liable for any incomplete or incorrect information in our information material except in 

the  case  of  wilful  act  or  omission  or  gross  negligence.  This  disclaimer  does  not  affect  any  claims  under  the

 Produkthaftungsgesetz (Product Liability Act).

certified quality

management system

PCI Visconal

®



Last revised in October 2020 

(German edition August 2020)

This version will become invalid immediately upon

the publication of a later version; 

you will always find the latest version on the

 Internet at www.pci-augsburg.de.



Yüklə 240,04 Kb.

Dostları ilə paylaş:




Verilənlər bazası müəlliflik hüququ ilə müdafiə olunur ©www.azkurs.org 2024
rəhbərliyinə müraciət

gir | qeydiyyatdan keç
    Ana səhifə


yükləyin